CG Drives & Automation 01-7491-01r0 Functional description 113
Over current F [25O]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Pump [25P]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Over Speed [25Q]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
External Motor Temperature [25R]
Delay time starts counting when the fault disappears. When
the time delay has elapsed, the alarm will be reset if the
function is active.
External Motor Trip Type [25S]
Select the preferred way to react to an alarm trip.
Liquid cooling low level [25T]
Delay time starts counting when the fault disappears. When
the time delay has elapsed, the alarm will be reset if the
function is active.
Liquid Cooling Low level Trip Type
[25U]
Select the preferred way to react to an alarm trip.
Brake Fault [25V]
Delay time starts counting when the fault disappears. When
the time delay has elapsed, the alarm will be reset if the
function is active.
Encoder [25W]
Encoder delay time, starts counting when the fault
disappears. When the time delay has elapsed, the alarm will
be reset if the function is active.
25O Over curr F
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
25P Pump
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
25Q Over speed
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
25R Ext Mot Temp
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
25S Ext Mot TT
Default: Trip
Selection: Same as menu [25B]
25T LC Level
Default: Off
Off 0 Off
1–3600 1–3600 1–3600 s
25U LC Level TT
Default: Trip
Selection: Same as menu [25B]
25V Brk Fault
Default Off
Off 0 Autoreset not activated.
1 - 3600s 1 - 3600 Brake fault auto reset delay time.
25W Encoder
Default: Off
Off 0 Off
1- 3600 1- 3600 1- 3600 s