22 Mounting CG Drives & Automation 01-7491-01r0
2.3 Cabinet mounting
2.3.1 Cooling
If the variable speed drive is installed in a cabinet, the rate of
airflow supplied by the cooling fans must be taken into
consideration.
2.3.2 Recommended free space in
front of cabinet
All cabinet mounted AC drives are designed in modules, so
called PEBBs. These PEBBs can be folded out to be
replaced. To be able to remove a PEBB in the future, we
recommend 1.30 meter (39.4 in) free space in front of the
cabinet, see fig. 28.
Fig. 28 Recommended free space in front of the cabinet
mounted AC drive.
Frame
Emotron FDU
Model
Flow rate
m
3
/h (ft
3
/min)
B 003 - 018 75 (144)
C - C2 025 – 031 120 (171)
C - C2 036 - 058 170 (100)
C69 002 - 025 170 (100)
C2(69) 002 - 025 170 (100)
D - D2 060 - 105 170 (100)
D69 033 - 058 170 (100)
D2(69) 033 - 058 170 (100)
E - E2 090 - 175 510 (300)
F - F2 205 - 295 800 (471)
FA - FA2 365 1020 (600)
F69 090 - 200 800 (471)
G 300 - 375 1020 (600)
H 430 - 500
1600 (942)
H69 250 - 400
I 600 - 750
2400 (1413)
I69 430 - 595
J 860 - 1K0
3200 (1883)
J69 650 - 800
KA 1K15 - 1K25
4000 (2354)
KA69 905 - 995
K 1K35 - 1K5
4800 (2825)
K69 1K2
L1K75
5600 (3296)
L69 1K4
M2K0
6400 (3767)
M69 1K6
N2K25
7200 (4238)
N69 1K8
O2K5
8000 (4709)
O69 2K0
P69 2K2 8800 (5179)
Q69 2K4 9600 (5650)
R69 2K6 10400 (6121)
S69 2K8 11200 (6592)
T69 3K0 12000 (7063)
NOTE: For the models 48-860/69-650 to 69-3K0 the
mentioned amount of air flow should be divided
equally over the cabinets.