CG Drives & Automation 01-7491-01r0 185
-100%AnOut1 has a negative 100% output value
65%AnOut2 has a 65% output value
The example in fig. 153 indicates that both the Analogue
outputs are active.
I/O board Status [728] - [72A]
Indicates the status for the additional I/O on option boards
1 (B1), 2 (B2) and 3 (B3).
Area D Stat [72B]
These menus are not visible in the control panel display.
Only used in EmoSoftCom PC-tool (optional) and can be
read via fieldbus or serial communication.
Area D LSB [72B1]
Status bits 0 to 15.
See Chapter 10.2.1 page 85.
Area D MSB [72B2]
Status bits 16 and up.
See Chapter 10.2.1 page 85.
VIO Status [72C]
Shows the values of the 8 Virtual IO´s in menu[560].
11.7.3 Stored values [730]
The shown values are the actual values built up over time.
Values are stored at power down and updated again at power
up.
Run Time [731]
Displays the total time that the AC drive has been in the
Run Mode.
Reset Run Time [7311]
Reset the run time counter. The stored information will be
erased and a new registration period will start.
Mains time [732]
Displays the total time that the AC drive has been connected
to the mains supply. This timer cannot be reset.
Energy [733]
Displays the total energy consumption since the last energy
reset [7331] took place.
NOTE: The shown percentages are absolute values
based on the full range/scale of the in- or output; so
related to either 0–10 V or 0–20 mA.
728 0rpm
IO B1
RE 000 DI100
Sby Rem/Rem
72C 0rpm
VIO Status
00000000
Sby Rem/Rem
731 Run Time
Unit: hh:mm:ss (hours: minutes: seconds)
Range: 00: 00: 00–262143: 59: 59
7311 Reset RunTm
Default: No
No 0
Yes 1
NOTE: After reset the setting automatically reverts to
“No”.
732 Mains Time
Unit: hh:mm:ss (hours: minutes: seconds)
Range: 00: 00: 00–262143: 59: 59
733 Energy
Unit: Wh (shows Wh, kWh, MWh or GWh)
Range:
0.0–1GWh,
Counter will restart at 0 after 1GWh