158 CG Drives & Automation 01-7491-01r0
Digital Input 2 [522] to Digital
Input 8 [528]
Same function as “DigIn 1[521]”. Default function for
DigIn 8 is Reset. For DigIn 3 to 7 the default function is
Off.
Additional digital inputs [529] to
[52H]
Additional digital inputs with I/O option board installed,
“B1 DigIn 1 [529]” - “B3 DigIn 3 [52H]”. B stands for
board and 1 to 3 is the number of the board which is related
to the position of the I/O option board on the option
mounting plate. The functions and selections are the same as
“DigIn 1 [521]”.
11.5.3 Analogue Outputs [530]
Submenu with all settings for the analogue outputs.
Selections can be made from application and AC drive
values, in order to visualize actual status. Analogue outputs
can also be used as a mirror of the analogue input. Such a
signal can be used as:
a reference signal for the next AC drive in a Master/Slave
configuration (see fig. 135).
a feedback acknowledgement of the received analogue
reference value.
AnOut1 Function [531]
Sets the function for the Analogue Output 1. Scale and
range are defined by AnOut1 Advanced settings [533].
Timer 2 35
Timer 2 will be activated on the rising edge
of this signal.
Timer 3 36
Timer 3 will be activated on the rising edge
of this signal.
Timer 4 37
Timer 4 will be activated on the rising edge
of this signal.
NOTE: For bipol function, input RunR and RunL
needs to be active and “Rotation [219]” must be set
to “R+L”.
Ta b l e 3 6
Parameter Set Set Ctrl 1 Set Ctrl 2
A00
B10
C01
D11
NOTE: To activate the parameter set selection, menu
241 must be set to DigIn.
522 DigIn 2
Default: RunR
Selection: Same as in menu DigIn 1
[521]
529 B1 Digin 1
Default: Off
Selection: Same as in menu DigIn 1 [521]
531 AnOut1 Fc
Default: Speed
Process Val 0
Actual process value according to
Process feedback signal.
Speed 1 Actual speed.
Torque 2 Actual torque.
Process Ref 3 Actual process reference value.
Shaft Power 4 Actual shaft power.
Frequency 5 Actual frequency.
Current 6 Actual current.
El power 7 Actual electrical power.
Output volt 8 Actual output voltage.
DC-voltage 9 Actual DC link voltage.
AnIn1 10
Mirror of received signal value on
AnIn1.
AnIn2 11
Mirror of received signal value on
AnIn2.
AnIn3 12
Mirror of received signal value on
AnIn3.
AnIn4 13
Mirror of received signal value on
AnIn4.
Speed Ref 14
Actual internal speed reference Value
after ramp and V/Hz.
Torque Ref 15
Actual torque reference value
(=0 in V/Hz mode)
AnMux1 16
Result of configured AnMux1 logical
block, see [621].
AnMux2 17
Result of configured AnMux2 logical
block, see [622].
IGBT Temp 18 Temperature of drive IGBT, see [71A].
NOTE: When selections AnIn1, AnIn2 …. AnIn4 is
selected, the setup of the AnOut (menu [532] or [535])
has to be set to 0-10V or 0-20mA. When the AnOut
Setup is set to e.g. 4-20mA, the mirroring is not
working correct.