Cerabar M, Deltabar M, Deltapilot M Operation
Endress+Hauser 55
"Simulate En/Disable/ENABLE_DISABLE" element, "Disabled" option), set "Simulation"
DIP switch to "OFF".
You can check your adjustment for the transmitter by means of the Simulation mode/
SIMULATION_MODE and Simulated Value/SIMULATED_VALUE parameters in the
Diagnostic Transducer Block. See Simulation mode/SIMULATION_MODE and Simulated
Value/SIMULATED_VALUE parameter description.
6.3.7 Resetting to factory settings (reset)
By entering a certain code, you can completely, or partially, reset the entries for the
parameters to the factory settings
1)
. Enter the code by means of the "Enter reset code (124)"
parameter (menu path: "Diagnosis" "Reset" "Enter reset code (124)" or "Diagnosis"
"Reset" "Enter reset code (124)").
There are various reset codes for the device. The following table illustrates which parameters
are reset by the particular reset codes. Operation must be unlocked to reset parameters
( ä 54).
Any customer-specific configuration carried out at the factory is not affected by a reset
(customer-specific configuration remains). If you want to change the customer-specific
configuration carried out at the factory, please contact Endress+Hauser Service.
1) The default value for the individual parameters is indicated in the parameter description ( ä 116 ff)
Reset code
1)
1) To be entered in "Diagnosis" "Reset" "Enter reset code (124)"
Description and effect
62 PowerUp reset (warm start)
The device is restarted.
Data are read back anew from the EEPROM (processor is initialized again).
Any simulation which may be running is ended.
333 User reset
This code resets all the parameters apart from:
Pd-tag. (022)
Linearization table
Operating hours (162)
Event logbook
Lo trim sensor (131)
Hi trim sensor (132)
Any simulation which may be running is ended.
The device is restarted.
7864 Total reset
This code resets all the parameters apart from:
Operating hours (162)
Event logbook
Lo trim sensor (131)
Hi trim sensor (132)
Any simulation which may be running is ended.
The device is restarted.