Commissioning Cerabar S PMP71 with 4 to 20 mA HART
36 Endress+Hauser
6.4 Pressure measurement
6.4.1 Information on pressure measurement
!
Note!
• There is a Quick Setup menu for the measuring mode Pressure which guides you through the
most important basic functions. With the setting in the MEASURING MODE parameter, you
specify which Quick Setup menu should be displayed. See also → ä 34, "Selecting language and
measuring mode".
• For a detailed description of the parameters, see Operating Instructions BA00413P
"Description of device functions"
– Table 6, POSITION ADJUSTMENT
– Table 7, BASIC SETUP
– Table 15, EXTENDED SETUP
• For differential pressure measurement, select the "Pressure" option by means of the MEASURING
MODE parameter. The operating menu is structured accordingly. See also → ä 52, "Operating
menu for onsite display and digital communication".
6.4.2 Quick Setup menu for Pressure measuring mode
P01-MIDxxxxx-19-xx-xx-EN-023
Fig. 21: Quick Setup menu for Pressure measuring mode
1)
1) 1)
2)
1) Display via on-site display only
2) Display via FieldCare
and HART handheld terminal only
SET LRV
SET URV
DAMPING VALUE
POS. INPUT VALUE
Pressure
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE MEASURING MODE
QUICK SETUP
MEASURING MODE
Level (not
for PMP71 with MID)
provided
Onsite operation Digital communication
Measured value display
Switch from the measured value display to GROUP
SELECTION with F.
Measured value display
Select QUICK SETUP menu.
GROUP SELECTION
Select MEASURING MODE parameter.
MEASURING MODE
Select "Pressure" option.
MEASURING MODE
Select "Pressure" option.
GROUP SELECTION
Select QUICK SETUP menu.
POS. INPUT VALUE
Due to orientation of the device, there may be a shift in
the measured value. For the POS. INPUT VALUE
parameter, specify the desired set point for the
MEASURED VALUE.
POS. INPUT VALUE
Due to orientation of the device, there may be a shift in
the measured value. For the POS. INPUT VALUE
parameter, specify the desired set point for the
MEASURED VALUE.