Installation Cerabar S PMP71 with 4 to 20 mA HART
14 Endress+Hauser
3.3.4 Rotating the housing
The housing can be rotated up to 380° by loosening the setscrew.
P01-PMx7xxxx-17-xx-xx-xx-000
Fig. 10: Aligning the housing
– T14 and T15 housing: Loosen setscrew with a 2 mm (0.08 in) Allen key.
Hygienic T17 housing: Loosen setscrew with a 3 mm (0.12 in) Allen key.
– Rotate housing (max. up to 380°).
– Retighten setscrew with a torque of 1 Nm (0.74 lbf ft).
3.3.5 Closing cover on hygienic stainless steel housing (T17)
P01-PMx7xxxx-17-xx-xx-xx-002
Fig. 11: Closing the cover
The covers for the terminal and electronics compartment are hooked into the casing and closed with
a screw. These screws should be hand-tightened (2 Nm, 1.48 lbf ft) to the stop to ensure that the
covers sit tightly.
3.4 Post-installation check
After installing the device, carry out the following checks:
Are all the screws firmly tightened?
Are the housing covers screwed down tight?