Cerabar S PMP71 with 4 to 20 mA HART Installation
Endress+Hauser 13
3.3.2 Seal for flange mounting
P01-FMD7xxxx-11-xx-xx-xx-002
Fig. 9: Mounting the versions with flange or diaphragm seal
1 Process isolating diaphragm
2Seal
#
Warning!
The seal is not allowed to press against the process isolating diaphragm as this could affect the
measurement result.
3.3.3 Wall and pipe-mounting (optional)
Endress+Hauser offers a mounting bracket for installing on pipes or walls.
P01-xMx5xxxx-06-xx-xx-xx-001
Please note the following when mounting:
• Devices with capillary tubes: mount capillaries with a bending radius of ≥ 100 mm (3.94 in).
• In the case of pipe mounting, the nuts on the bracket must be tightened uniformly with a torque
of at least 5 Nm (3.69 lbf ft).
52 (2.05)
140 (5.51)
122 (4.8)
70 (2.76)
6 (0.24)
mm (in)