Appendix Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART
108 Endress+Hauser
10.2 Description of parameters
!
Note!
This section describes the parameters in the order they are arranged in the "Expert" operating menu.
Parameters (or parameter numbers) in italics are read-only parameters and cannot be edited.
Specific settings, such as the measuring mode, dry or wet calibration, or hardware locking,
determine whether these parameters are displayed.
Expert
10.2.1 System
Expert È System
Parameter name Description
Direct access (119)
Entry
Enter the direct access code to go directly to a parameter.
Options:
A number between 0 and 999 (only valid entries are recognized)
Factory setting:
0
Note:
For direct access, it is not necessary to enter leading zeros.
Parameter name Description
Code definition (023)
Entry
Use this function to enter a release code with which the device can be unlocked.
Options:
A number between 0 and 9999
Factory setting:
0
Lock switch (120)
Display
Displays the status of DIP switch 1 on the electronic insert.
You can lock or unlock parameters relevant to the measured value with DIP switch 1. If
operation is locked by means of the "Operator code" (021) parameter, you can only
unlock operation again by means of this parameter.
Display:
On (locking switched on)
Off (locking switched off)
Factory setting:
Off (locking switched off)
Operator code (021)
Entry
Use this function to enter a code to lock or unlock operation.
Options:
To lock operation: enter a number between 1 and 9999 provided the release code = 0;
then a number release code.
To unlock operation: enter the number 0.
!
Note!
The release code is "0" in the order configuration. Another release code can be defined in
the "Code definition" parameter.
If the user has forgotten the release code, it can be made visible again by entering the
number sequence "5864".
Factory setting:
0

Table of Contents

Other manuals for Endress+Hauser Deltabar M PMD55

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Deltabar M PMD55 and is the answer not in the manual?

Endress+Hauser Deltabar M PMD55 Specifications

General IconGeneral
BrandEndress+Hauser
ModelDeltabar M PMD55
CategoryTransmitter
LanguageEnglish

Related product manuals