Appendix Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART
126 Endress+Hauser
Expert È Application È Totalizer 1 (Deltabar M)
!
Note!
With the "Flow in %" flow type setting, the totalizer is not avaialble and is not displayed at this
position.
Parameter name Description
Eng. unit totalizer 1
(058) (059) (060) (061)
Selection
Select unit for totalizer 1.
Options
Depending on the settinbg in the "Flow meas. type" (044) parameter this parameter offers
a list of volume, norm volume, standard volume and mass units. When a new volume or
mass unit is selected, totalizuer-specific parameters are converted and displayed with the
new unit within a unit group. When the flow mode is change, the totalizer value is not
converted.
The Direct Access Code depends on the selection in the "Flow meas. type" (044)
parameter:
(058): Flow. meas. type "Mass"
(059): Flow. meas. type "Volume norm. cond."
(060): Flow. meas. type "Volume std. cond."
(061): Flow. meas. type "Volume process cond."
Factory setting:
m
3
Totalizer 1 mode (175) Define the behavior of the totalizer.
Options:
Balanced: Integration of all measured flows (positive and negative)
Pos. flow only: only positive flows are integrated.
Neg. flow only: only negative flows are integrated.
Hold: No flow is integrated. The totalizer keeps its current value.
Factory setting:
Pos. flow only
Totalizer 1 failsafe (176) Define the behavior of the totalizer in the case of an error.
Options:
Run: Totalizing is continued.
Hold: The totalizer is stopped and keeps its current value.
Reset Totalizer 1 (062)
Selection
You reset totalizer 1 to zero with this parameter.
Selection:
Abort (do not reset)
•Reset
Factory setting:
Abort
Totalizer 1 (063)
Display
Displays the total flow value of totalizer 1. You can reset the value with the "Reset
totalizer 1" (062) parameter. The "Totalizer 1 overflow" (064) parameter displays the
overflow.
Example: The value123456789 m
3
is indicated as follows:
Totalizer 1: 3456789 m
3
Totalizer 1 overflow: 12 E7 m
3
Totalizer 1 overflow (064)
Display
Displays the overflow value of totalizer 1.
See also "Totalizer 1" (063).

Table of Contents

Other manuals for Endress+Hauser Deltabar M PMD55

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Deltabar M PMD55 and is the answer not in the manual?

Endress+Hauser Deltabar M PMD55 Specifications

General IconGeneral
BrandEndress+Hauser
ModelDeltabar M PMD55
CategoryTransmitter
LanguageEnglish

Related product manuals