Cerabar M, Deltabar M, Deltapilot M / 4...20 mA HART Operation
Endress+Hauser 47
Accepting the pressure present
Example: setting position adjustment
P01-PMD55xxx-19-xx-xx-xx-008
The new value for the upper range value is 50.0 mbar (0.75
psi).
– You exit the edit mode for the parameter with "E" .
– You can get back to the editing mode with "+" or
"–".
Local display Operation
P01-PMD55xxx-19-xx-xx-xx-009
The pressure for position adjustment is present at the
device.
P01-PMD55xxx-19-xx-xx-xx-010
Use "+" or "–" to switch to the "Confirm" option. The active
option is highlighted in black.
P01-PMD55xxx-19-xx-xx-xx-011
Accept the pressure present as position adjustment with the
"E" key. The device confirms the adjustment and goes back
to the "Pos. zero adjust" parameter.
P01-PMD55xxx-19-xx-xx-xx-009
Exit the edit mode for the parameter with "E" .
Local display Operation