Deltabar PMD75B HART Diagnostics and troubleshooting
Endress+Hauser 61
11.6.1 List of diagnostic events
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of sensor
062 Sensor connection faulty Check sensor connection F Alarm
081 Sensor initialization
faulty
1. Restart device
2. Contact service
F Alarm
100 Sensor error 1. Restart the device
2. Contact Endress+Hauser
Service
F Alarm
101 Sensor temperature 1. Check process temperature
2. Check ambient temperature
F Alarm
102 Sensor incompatible error 1. Restart device
2. Contact service
F Alarm
Diagnostic of electronic
242 Firmware incompatible 1. Check software
2. Flash or change main
electronics module
F Alarm
252 Module incompatible 1. Check if correct electronic
modul is plugged
2. Replace electronic module
F Alarm
263 Incompatibility detected Check electronic module type M Warning
270 Main electronics
defective
Replace main electronics F Alarm
272 Main electronics faulty 1. Restart device
2. Contact service
F Alarm
273 Main electronics
defective
1. Transfer data or reset device
2. Contact service
F Alarm
282 Data storage inconsistent 1. Restart device
2. Contact service
F Alarm
283 Memory content
inconsistent
1. Transfer data or reset device
2. Contact service
F Alarm
287 Memory content
inconsistent
1. Restart device
2. Contact service
M Warning
311 Electronic failure Maintenance required!
1. Do not perform reset
2. Contact service
M Warning
Diagnostic of configuration
410 Data transfer failed 1. Check connection
2. Retry data transfer
F Alarm
412 Processing download Download active, please wait C Warning
431 Trim required Carry out trim C Warning
435 Linearization faulty Check linearization table F Alarm
437 Configuration
incompatible
1. Restart device
2. Contact service
F Alarm
438 Dataset different 1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
M Warning
441 Current output out of
range
1. Check process
2. Check current output settings
S Warning

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Deltabar PMD75B HART and is the answer not in the manual?

Endress+Hauser Deltabar PMD75B HART Specifications

General IconGeneral
BrandEndress+Hauser
ModelDeltabar PMD75B HART
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals