EasyManuals Logo

Endress+Hauser Deltabar PMD75B HART User Manual

Endress+Hauser Deltabar PMD75B HART
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
Deltabar PMD75B HART Technical data
Endress+Hauser 73
Vibration resistance Single compartment housing
Measuring range Sine wave oscillation IEC 61298-3:2008 Shock
10 mbar (0.15 psi) and 30 mbar (0.45 psi) (only up to
PN100)
10 Hz to 60 Hz: ±0.21 mm (0.0083 in)
60 Hz to 2000 Hz: 3 g
30 g
0.1 to 250 bar (1.5 to 3 750 psi) 10 Hz to 60 Hz: ±0.35 mm (0.0138 in)
60 Hz to 1000 Hz: 5 g
30 g
Aluminum dual compartment housing
Measuring range Sine wave oscillation IEC 61298-3:2008 Shock
10 mbar (0.15 psi) and 30 mbar (0.45 psi) 10 Hz to 60 Hz: ±0.21 mm (0.0083 in)
60 Hz to 2000 Hz: 3 g
30 g
0.1 to 250 bar (1.5 to 3 750 psi) 10 Hz to 60 Hz: ±0.35 mm (0.0138 in)
60 Hz to 1000 Hz: 5 g
30 g
Stainless steel dual compartment housing
Measuring range Sine wave oscillation IEC 61298-3:2008 Shock
10 mbar (0.15 psi) and 30 mbar (0.45 psi) (only up to
PN63)
10 Hz to 60 Hz: ±0.15 mm (0.0059 in)
60 Hz to 500 Hz: 1 g
15 g
0.1 to 250 bar (1.5 to 3 750 psi) 10 Hz to 60 Hz: ±0.15 mm (0.0059 in)
60 Hz to 500 Hz: 2 g
15 g
Dual compartment housing, L-shape
Sine wave oscillation IEC 61298-3:2008 Shock
10 Hz to 60 Hz: ±0.21 mm (0.0083 in)
60 Hz to 2000 Hz: 3 g
30 g
Electromagnetic
compatibility (EMC)
Electromagnetic compatibility as per EN 61326 series and NAMUR recommendation
EMC (NE21)
With regard to the safety function (SIL), the requirements of EN 61326-3-x are satisfied
Maximum deviation with interference influence: < 0.5% of span with full measuring
range (TD 1:1)
For more details refer to the EU Declaration of Conformity.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Deltabar PMD75B HART and is the answer not in the manual?

Endress+Hauser Deltabar PMD75B HART Specifications

General IconGeneral
BrandEndress+Hauser
ModelDeltabar PMD75B HART
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals