Loading...
Ecograph T, RSG35 Appendix
Endress+Hauser 79
Temp. unit
Navigation Expert → System → Temp. unit
Direct access code: 100001-000
Description Selection of temperature unit. All directly connected thermocouples or resistance
thermometers (RTD) are displayed in the preset engineering units.
Options °C, °F, K
Factory setting °C
Decimal separator
Navigation Expert → System → Decimal separator
Direct access code: 100003-000
Description Select in which form the decimal separator character is to be displayed.
Options Comma, point
Factory setting Comma
Fault switching
Navigation Expert → System → Fault switching
Direct access code: 100002-000
Description If the device detects a system error (e.g. hardware defect) or a fault (e.g. cable open
circuit), the selected output switches.
Options Not used, Relay x
All the available relays are displayed
Factory setting Relay 1
Keyboard layout
Navigation Expert → System → Keyboard layout
Direct access code: 100020/000
Description Please select the keyboard layout. Only relevant if external keyboard is used.