Proline Promag P 500 HART System integration
Endress+Hauser 93
Parameter Description Selection / User entry Factory setting
Burst variable 0 For HART command 9 and 33: select the
HART device variable or the process variable.
Volume flow
Mass flow
Corrected volume flow
Flow velocity
Conductivity
*
Electronic temperature
Totalizer 1
Totalizer 2
Totalizer 3
Density
HART input
Percent of range
Measured current
Primary variable (PV)
Secondary variable (SV)
Tertiary variable (TV)
Quaternary variable (QV)
Not used
Volume flow
Burst variable 1 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 2 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 3 For HART command 9 and 33: select the
HART device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 4 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 5 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 6 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst variable 7 For HART command 9: select the HART
device variable or the process variable.
See the Burst variable 0
parameter.
Not used
Burst trigger mode Select the event that triggers burst message
X.
Continuous
Window
Rising
Falling
On change
Continuous
Burst trigger level Enter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Signed floating-point number
Min. update period Enter the minimum time span between two
burst commands of burst message X.
Positive integer 1 000 ms
Max. update period Enter the maximum time span between two
burst commands of burst message X.
Positive integer 2 000 ms
* Visibility depends on order options or device settings