Operating menu and parameter description iTEMP TMT82
76 Endress+Hauser
Additional information Standard
The output current increases with increasing temperatures
inverted
The output current decreases with increasing temperatures
Options Standard
inverted
Factory setting Standard
Out of range category
Navigation Setup → Advanced setup → Current output→ Out of range category
Expert → Output → Out of range category
Description Use this function to select the category (status signal) as to how the device reacts when
the value is outside the set measuring range.
Options Out of specification (S)
Maintenance required (M)
Failure (F)
Factory setting Maintenance required (M)
Failure mode
Navigation Setup → Advanced setup → Current output→ Failure mode
Expert → Output → Failure mode
Description Use this function to select the signal on alarm level of the current output in the event of an
error.
Additional information If Max. is selected, the signal on alarm level is specified using the Failure current
parameter.
Options Min.
Max.
Factory setting Max.
Failure current
Navigation Setup → Advanced setup → Current output→ Failure current
Expert → Output → Failure current
Prerequisite The Max. option is enabled in the Failure mode parameter.