iTEMP TMT82 Operating menu and parameter description
Endress+Hauser 81
Factory settings Off
Decimal places 3
Navigation Setup → Advanced setup → Display → Decimal places 3
Expert → System → Display → Decimal places 3
Prerequisite A measured value is specified in the Value 3 display parameter.
Description Use this function to select the number of decimal places displayed for the display value.
This setting does not affect the accuracy of the device for measuring or calculating the
value.
If Automatic is selected, the maximum possible number of decimal places is always
shown on the display.
Options: x
x.x
x.xx
x.xxx
x.xxxx
Automatic
Factory settings Automatic
"SIL" submenu
This menu only appears if the device was ordered with the 'SIL mode' option. The SIL
option parameter indicates whether the device can be operated in the SIL mode. To
enable the SIL mode for the device, menu-guided operation for Enable SIL must be
performed.
A detailed description is provided in the Functional Safety Manual SD01172T.
SIL option
Navigation Setup → Advanced setup → SIL → SIL option
Description Indicates whether the device has been ordered with SIL certification. SIL certificate of the
device
The SIL option is required to operate the device in the SIL mode.
Options No
Yes
Factory setting No
Operational state