iTEMP TMT82 Operating menu and parameter description
Endress+Hauser 83
Description Use this function to display the SIL checksum entered.
The SIL checksum displayed can be used to check the device configuration. If 2
devices have identical configurations, the SIL checksum is also identical. This can
make for easy device replacement because if the checksum is the same, the device
configuration is guaranteed to be identical too.
Timestamp SIL configuration
Navigation Setup → Advanced setup → SIL → Timestamp SIL configuration
Description Use this function to enter the date and time when safe parameterization has been
completed and the SIL checksum has been calculated.
The date and time must be entered manually. This information is not generated
automatically by the device.
User entry DD.MM.YYYY hh:mm
Factory setting 0
SIL startup mode
Navigation Setup → Advanced setup → SIL → SIL startup mode
Description Setting for repeated automatic device startup in the SIL mode, e.g. after a power-cycle.
The "Not active" setting requires the user to enter the SIL checksum manually in
order to be able to start the device again in SIL mode.
Options Not active
Active
Factory setting Not active
SIL HART mode
Navigation Setup → Advanced setup → SIL → SIL HART mode
Description Setting for HART
®
communication in the SIL mode. The "HART not active" setting disables
HART
®
communication in the SIL mode (only 4 to 20 mA communication is active).
Options HART not active
HART active
Factory setting HART active