Operating menu and parameter description iTEMP TMT82
82 Endress+Hauser
Navigation Setup → Advanced setup → SIL → Operational state
Description Displays the device operational state in the SIL mode.
Display Checking SIL option
Startup normal mode
Wait for checksum
Self diagnostic
Normal mode
Download active
SIL mode active
Safe para start
Safe param running
Save parameter values
Parameter check
Reboot pending
Reset checksum
Safe state - Active
Download verification
Upload active
Safe state - Passive
Safe state - Panic
If the device is restarted with the setting "SIL startup mode → Not active", "Wait for
checksum" appears in this parameter. The SIL checksum must be entered manually
here.
Factory setting Checking SIL option
Enter SIL checksum
Navigation Setup → Advanced setup → SIL → Enter SIL checksum
Description Use this function to enter the SIL checksum during safe parameterization and startup in
conjunction with the parameter setting "SIL startup mode → Not active".
If the parameter setting is "SIL startup modus → Active" and the value '0' is entered,
automatic startup is aborted and the SIL settings are discarded.
User entry 0 ... 65535
Factory setting 0
SIL checksum
Navigation Setup → Advanced setup → SIL → SIL checksum