Operating menu and parameter description iTEMP TMT82
82 Endress+Hauser
Navigation Setup → Advanced setup → SIL → Operational state
Description Displays the device operational state in the SIL mode.
Display • Checking SIL option
• Startup normal mode
• Wait for checksum
• Self diagnostic
• Normal mode
• Download active
• SIL mode active
• Safe para start
• Safe param running
• Save parameter values
• Parameter check
• Reboot pending
• Reset checksum
• Safe state - Active
• Download verification
• Upload active
• Safe state - Passive
• Safe state - Panic
If the device is restarted with the setting "SIL startup mode → Not active", "Wait for
checksum" appears in this parameter. The SIL checksum must be entered manually
here.
Factory setting Checking SIL option
Enter SIL checksum
Navigation Setup → Advanced setup → SIL → Enter SIL checksum
Description Use this function to enter the SIL checksum during safe parameterization and startup in
conjunction with the parameter setting "SIL startup mode → Not active".
If the parameter setting is "SIL startup modus → Active" and the value '0' is entered,
automatic startup is aborted and the SIL settings are discarded.
User entry 0 ... 65535
Factory setting 0
SIL checksum
Navigation Setup → Advanced setup → SIL → SIL checksum