iTEMP TMT82 Operating menu and parameter description
Endress+Hauser 77
Description Use this function to set the value the current output adopts in an alarm condition.
User entry 21.5 to 23.0 mA
Factory setting 22.5
Current trimming 4 mA
Navigation Setup → Advanced setup → Current output→ Current trimming 4 mA
Expert → Output → Current trimming 4 mA
Description Use this function to set the correction value for the current output at the start of the
measuring range at 4 mA.→  75
User entry 3.85 to 4.15 mA
Factory setting 4 mA
Current trimming 20 mA
Navigation Setup → Advanced setup → Current output→ Current trimming 20 mA
Expert → Output → Current trimming 20 mA
Description Use this function to set the correction value for the current output at the end of the
measuring range at 20 mA.→  75
User entry 19.850 to 20.15 mA
Factory setting 20.000 mA
"Display" submenu
The settings for displaying the measured value on the optional plug-in display (only for
head transmitter) are made in the "Display" menu.
These settings do not have any effect on the output values of the transmitter. They
are only used to configure how information is shown on the display.
Display interval
Navigation Setup → Advanced setup → Display → Display interval
Expert → System → Display → Display interval