Integrating the transmitter via the HART
®
protocol
iTEMP TMT82
30 Endress+Hauser
7
Integrating the transmitter via the HART
®
protocol
For secure HART
®
communication in accordance with functional safety as defined in
IEC 61508 (SIL mode), measured values are sent securely from the transmitter via the
HART
®
protocol to a connected control system where they are processed further in a
secure manner. Secure HART
®
communication works using special HART
®
commands
that are only available in the SIL mode.
The secure HART
®
protocol includes technologies, that are licenced by Rockwell
Automation.
For more information please refer to the Functional Safety Manual SD01172T/09.
Version data for the device
Firmware version 01.01.zz On the title page of the Operating instructions
On nameplate →  1,  8
Parameter firmware version
Diagnostics → Device info→ Firmware version
Manufacturer ID 0x11 Manufacturer ID parameter
Diagnostics → Device info→ Manufacturer ID
Device type ID 11CC Device type parameter
Diagnostics → Device info → Device type
HART protocol revision 7.0 ---
Device revision 2 On transmitter nameplate →  1,  8
Device revision parameter
Diagnostics → Device info → Device revision
The suitable device description file (DD) for the individual operating tools is listed in the
table below, along with information on where the file can be acquired.
Operating tools
Operating tool Sources for obtaining device descriptions (DD)
FieldCare www.endress.com → Download Area
CD–ROM (contact Endress+Hauser)
DVD (contact Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
www.endress.com → Download Area
SIMATIC PDM
(Siemens)
www.endress.com → Download Area
Field Communicator 375, 475
(Emerson Process Management)
Use update function of handheld terminal
FieldXpert SFX350, SFX370
(Endress+Hauser)
Use update function of handheld terminal
7.1 HART device variables and measured values
The following measured values are assigned to the device variables at the factory:
Device variables for temperature measurement
Device variable Measured value
Primary device variable (PV) Sensor 1
Secondary device variable (SV) Device temperature