Operating menu and parameter description iTEMP TMT82
84 Endress+Hauser
Force safe state
Navigation Setup → Advanced setup → SIL → Force safe state
Prerequisite The Operational state parameter displays SIL mode active.
Description During SIL proof testing this parameter is used to test error detection and the safe state of
the device.
A detailed description of SIL proof testing is provided in the Functional Safety
Manual SD01172T/09.
Options On
Off
Factory setting Off
"Administration" submenu
Device reset
Navigation Setup → Advanced setup → Administration → Device reset
Expert → System → Device reset
Description Use this function to reset the device configuration - either entirely or in part - to a defined
state.
Options Not active
No action is executed and the user exits the parameter.
To factory defaults
All the parameters are reset to the factory setting.
To delivery settings
All the parameters are reset to the order configuration. The order configuration can
differ from the factory setting if customer-specific parameter values were defined when
the device was ordered.
Restart device
The device is restarted but the device configuration remains unchanged.
Factory setting Not active
Define device write protection code
Navigation Setup → Advanced setup → Administration → Define device write protection code
Expert → System → Define device write protection code