Commissioning (block-based operation) Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
112 Endress+Hauser
D
L
L
L
F
L
I
UP
D
I
LN
E
R
0%
100%
DK (DC )
2 2
DK DC
1 1
( )
A0011177
27 Configuration parameters for interface measurements
R = Reference pioint of the measurement D
I
= Distance of interface (Distance from reference point to lower
medium)
E = Empty calibration (= zero point) L
I
= Interface level
F = Full calibration (= span) D
L
= Distance from reference point R to total level
LN = Length of probe L
L
= total level
UP = Thickness of upper medium
Schritt Block Parameter Aktion
1 SETUP (TRDSUP) Distance unit (distance_unit) Select distance unit.
Selection:
• 1010: m
• 1013: mm
• 1018: in
• 1019: ft
2 SETUP (TRDSUP) Operating mode (operating_mode)
1)
Select 32938: Interface.
3 SETUP (TRDSUP) Tank type (tank_type) Select tank type.
Selection:
• 32816: Bypass / pipe
• 33288: Metallic
• 33302: Coaxial
• 33432: Twin rope
• 33433: Twin rod
• 33437: Rope centering disc metallic
• 33438: Rod centering disc metallic
• 33441: Non metallic
• 33444: Mounted outside
4 SETUP (TRDSUP) Tube diameter (tube_diameter)
2)
Enter the diameter of the bypass or
stilling well.
5 SETUP (TRDSUP) Tank level (tank_level) Select tank level.
Selection:
• 32919: Fully flooded (typical for
bypass measurements)
• 33021: Partially filled (typical for
measurements directly in tank)