Integration into a FOUNDATION Fieldbus network Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
86 Endress+Hauser
Name Label Index Data type Size
(Bytes)
Storage
Class
Write
access
MODE_BL
K
Description
distance_unit Distance unit 51 ENUM16 2 Static x OOS
interface Interface 70 FLOAT 4 Dynamic
level_unit Level unit 58 ENUM16 2 Static x OOS
output_unit_after_lineariza
tion
Unit after linearization 62 ENUM16 2 Static
level_linearized Level linearized 64 FLOAT 4 Dynamic
present_probe_length Present probe length 87 FLOAT 4 Dynamic x AUTO
level Level 60 FLOAT 4 Dynamic
interface_linearized Interface linearized 73 FLOAT 4 Dynamic
decimal_places_menu_ro Decimal places menu 93 ENUM16 2 Static x AUTO
locking_status Locking status 96 BIT_ENU
M16
2 Dynamic
medium_type_ro Medium type 92 ENUM16 2 Static x OOS
9.6.2 Advanced Setup Transducer Block
Name Label Index Data type Size
(Bytes)
Storage
Class
Write
access
MODE_BL
K
Description
calculated_dc_value Calculated DC value 61 FLOAT 4 Dynamic
blocking_distance Blocking distance 55 FLOAT 4 Static x OOS
interface_property Interface property 57 ENUM16 2 Static x OOS
dc_value_lower_medium DC value lower medium 58 FLOAT 4 Static x OOS
medium_type Medium type 50 ENUM16 2 Static x OOS
present_probe_length_ro Present probe length 80 FLOAT 4 Dynamic x AUTO
confirm_probe_length Confirm probe length 79 ENUM16 2 Static x OOS
process_property Process property 52 ENUM16 2 Static x OOS
advanced_process_conditio
ns
Advanced process
conditions
53 ENUM16 2 Static x OOS
meas_upper_iface_thickne
ss
Measured upper interface
thickness
60 FLOAT 4 Dynamic
manual_interface_thicknes
s
Manual interface thickness 59 FLOAT 4 Static x OOS
medium_property Medium property 51 ENUM16 2 Static x OOS
use_calculated_dc_value Use calculated DC value 62 ENUM16 2 Static x OOS
linearization_type Linearization type 71 ENUM16 2 Static x OOS
activate_table Activate table 70 ENUM16 2 Static x OOS
table_mode Table mode 69 ENUM16 2 Static x OOS
custom_table_sel_level Level 73 FLOAT 4 Static x OOS
custom_table_sel_value Customer value 74 FLOAT 4 Static x OOS
unit_after_linearization Unit after linearization 63 ENUM16 2 Static x OOS
free_text Free text 64 STRING Static x AUTO
diameter Diameter 66 FLOAT 4 Static x OOS
output_echo_lost Output echo lost 76 ENUM16 2 Static x OOS
intermediate_height Intermediate height 67 FLOAT 4 Static x AUTO