Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 111
Step Block Parameter Action
5 SETUP (TRDSUP) Medium group
(medium_group)
Select medium group.
Selection:
• 316: water based (DC>4)
• 256: other (DC≥ 1.9)
3)
6 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the reference point
R and the minimum level (0%).
7 SETUP (TRDSUP) Full calibration
(full_calibration)
Enter distance F between the minimum (0%)
and maximum (100%) level.
8 SETUP (TRDSUP) Level (level) Displays the measured level L.
9 SETUP (TRDSUP) Distance (filtered_dist_val) Displays the distance D between the reference
point R and the level L.
10 SETUP (TRDSUP) Signal quality
(signal_quality)
Displays the signal quality of the level echo.
11 SETUP (TRDSUP) Confirm distance
(confirm_distance)
Compare the displayed distance to the real
distance in order to start the recording of the
mapping curve.
Selection:
• 179: Manual map
• 32847: Delete all
• 32859: Distance ok
• 32860: Distance too big
• 32861: Distance too small
• 32862: Distance unknown
• 33100: Tank empty
1) only available for devices with "interface measurement" application package
2) only available for coated probes and "Tank type" = "Bypass/pipe"
3) If required, lower DCs can ben entered into the "DC value (dc_value)" parameter. However, for DC<1.6 the
measuring range may be reduced; for details please contact Endress+Hauser.
12.7 Configuration of an interface measurement
Only devices with the respective software option can be used for interface
measurements. This option is selected in the product structure: Feature 540
"Application package", option EB "Interface measurement".
The Setup method can also be used to configure the measurement. It is called up via
the SETUP (TRDSUP) transducer block.