Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 243
17.4.8 "Device check" submenu
Navigation Diagnostics → Device check
Start device check
Navigation Diagnostics → Device check → Start dev. check
Description Start a device check.
Selection • No
• Yes
Factory setting No
Additional information In the case of a lost echo a device check can not be performed.
Result device check
Navigation Diagnostics → Device check → Result dev.check
Description Displays the result of the device check.
Additional information Meaning of the display options
• Installation ok
Measurement possible without restrictions.
• Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the
signal amplitudes.
• Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check
the mounting position of the device and the dielectric constant of the medium.
• Check not done
No device check has been performed.
Last check time
Navigation Diagnostics → Device check → Last check time
Description Displays the operating time at which the last device check has been performed.