Operating menu Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
242 Endress+Hauser
Selection Off
On
Factory setting Off
Switch status
Navigation  Expert → Diagnostics → Simulation → Switch status
Prerequisite Switch output simulation (→  241) = On
Description Define the switch state to be simulated.
Selection Open
Closed
Factory setting Open
Additional information The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.
Simulation device alarm
Navigation  Expert → Diagnostics → Simulation → Sim. alarm
Description Switch alarm simulation on or off.
Selection Off
On
Factory setting Off
Additional information When selecting the On option, the device generates an alarm. This helps to check the
correct output behavior of the device in the case of an alarm.
An active simulation is indicated by the diagnostic message C484 Simulation failure
mode.