Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 113
Schritt Block Parameter Aktion
6 SETUP (TRDSUP) Distance to upper connection
(distance_to_upper_connection)
For measurements in bypasses:
Enter the distance from the
reference point R to the lower edge
of the upper connection.
Otherwise: Keep the factory setting.
7 SETUP (TRDSUP) DC value (dc_value) Enter dielectric constant of the upper
medium.
8 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the
reference point R and the minimum
level (0%).
9 SETUP (TRDSUP) Full calibration (full_calibration) Enter distance F between the
minimum (0%) and maximum (100%)
level.
10 SETUP (TRDSUP) Level (level) Displays the measured level L.
11 SETUP (TRDSUP) Interface (interface) Displays the interface height L
I
.
12 SETUP (TRDSUP) Distance (filtered_dist_val) Displays the distance D between the
reference point R and the level L.
13 SETUP (TRDSUP) Interface distance
(interface_distance)
Displays the distance D
I
between the
reference point R and the interface L
I
.
14 SETUP (TRDSUP) Signal quality (signal_quality) Displays the signal quality of the level
echo.
15 SETUP (TRDSUP) Confirm distance (confirm_distance) Compare the displayed distance to the
real distance in order to start the
recording of the mapping curve.
Selection:
179: Manual map
32847: Delete all
32859: Distance ok
32860: Distance too big
32861: Distance too small
32862: Distance unknown
33100: Tank empty
1) only available for devices with "interface measurement" application package
2) only available for coated probes and "Tank type" = "Bypass/pipe"
12.8 Configuration of the on-site display
12.8.1 Factory settings of the on-site display for level measurements
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display 1 value, max. size 1 value, max. size
Value 1 display Levele linearized Levele linearized
Value 2 display Distance Distance
Value 3 display Current output 1 Current output 1
Value 4 display None Current output 21
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.