Mounting Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
22 Endress+Hauser
6 Mounting
6.1 Mounting requirements
6.1.1 Suitable mounting position
A
C
1
2 3
4
B
A0012606
 4 Mounting requirements for Levelflex
Mounting distances
Distance (A) between wall and rod or rope probe:
for smooth metallic walls: > 50 mm (2 in)
for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel
for concrete walls: > 500 mm (20 in), otherwise the available measuring range may be
reduced.
Distance (B) between rod or rope probe and internal fittings in the vessel: >
300 mm (12 in)
When using more than one Levelflex:
Minimum distance between the sensor axes: 100 mm (3.94 in)
Distance (C) from end of probe to bottom of the vessel:
Rope probe: > 150 mm (6 in)
Rod probe: > 10 mm (0.4 in)
Coax probe: > 10 mm (0.4 in)
For coax probes the distance to the wall and to internal fittings is arbitrary.