Commissioning (block-based operation) Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
116 Endress+Hauser
12.10.1 Groups of events
The diagnostic messages are classified into 16 groups according to the source and severity
of the respective event. A default diagnostic category is allocated to each group. Each
group is also represented by one bit of the allocation parameters.
Severity of the
event
Default diagnostic category Source of the
event
Bit Events within the group
Highest severity Failure (F) Sensor 31 • F003: Broken probe detected
• F046: Build-up detected
• F083: Memory content
• F104: HF cable
• F105: HF cable
• F106: Sensor
Electronics 30 • F242: Software incompatible
• F252: Modules incompatible
• F261: Electronic modules
• F262: Module connecting
• F270: Main electronic failure
• F271: Main electronic failure
• F272: Main electronic failure
• F273: Main electronic failure
• F275: I/O-Modul failure
• F276: I/O module failure
• F282: Datenspeicher
• F283: Electronic memory
• F311: Memory content
Configuration 29 • F410: Data transfer
• F411: Up-/download
• F435: Linearization
• F437: Configuration incompatible
Process 28 • F803: Current loop 1
• F825: Current loop 1
• F936: EMC interference
• F941: Echo lost
1)
• F970: Linearization
1) This event can be removed from the group in order to define its behavior individually; see section
"Configurable area".
Severity of the
event
Default diagnostic category Source of the
event
Bit Events within the group
High severity Function check (C) Sensor 27 not used in Levelflex
Electronics 26 not used in Levelflex
Configuration 25 • C411: Up-/download
• C431: Trim
• C484: Simulation failure mode
• C485: Simulation measured value
• C491: Simulation current output
• C585: Simulation distance
Process 24 not used in Levelflex
Severity of the
event
Default diagnostic category Source of the
event
Bit Events within the group
Low severity Out of specification (S) Sensor 23 not used in Levelflex
Electronics 22 not used in Levelflex