Commissioning via operating menu Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
98 Endress+Hauser
11.4 Configuration of a level measurement
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0011360
 22 Configuration parameters for level measurements in liquids
LN Length of probe
R Reference point of the measurement
D Distance
L Level
E Empty calibration (= Zero point)
F Full calibration (= Span)
If for rope probes the DC value is less than 7, then measurement is not possible in the
area of the straining weight. In these cases, the maximum recommended value for the
empty calibration E is LN - 250 mm (LN - 10 in).
1. Setup → Device tag
Enter tag for measuring point.
2. For devices with "interface measurement" application package:
Navigate to:Setup → Operating mode
Select Level option.
3. Navigate to: Setup → Distance unit
Select distance unit.
4. Navigate to: Setup → Tank type
Select tank type.
5. For Tank type = Bypass / pipe:
Navigate to: Setup → Tube diameter
Enter the diameter of the bypass or stilling well.
6. Navigate to: Setup → Medium group
Select medium group: (Water based (DC >= 4) or Others)
7. Navigate to: Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
8. Navigate to: Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
9. Navigate to: Setup → Level
Displays the measured level L.