Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 241
Description of parameters
Navigation Expert → Diagnostics → Simulation
Assign measurement variable
Navigation Expert → Diagnostics → Simulation → Assign meas.var.
Description Selct process variable to be simulated.
Selection • Off
• Level
• Interface
*
• Level linearized
• Interface linearized
• Thickness linearized
Factory setting Off
Additional information • The value of the variable to be simulated is defined in the Process variable value
parameter (→ 241).
• If Assign measurement variable ≠ Off, a simulation is active. This is indicated by a
diagnotic message of the Function check (C) category.
Process variable value
Navigation Expert → Diagnostics → Simulation → Proc. var. value
Prerequisite Assign measurement variable (→ 241) ≠ Off
Description Specify value of the process value being simulated.
User entry Signed floating-point number
Factory setting 0
Additional information Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
Switch output simulation
Navigation Expert → Diagnostics → Simulation → Switch sim.
Description Switch the simulation of the switch output on or off.