Commissioning (block-based operation) Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
120 Endress+Hauser
 29 Changed state of the "Fail Map" and "Check Map" columns
Make sure that for each group the corresponding bit is set to 1 in at least one of the
allocation parameters. Otherwise no event category is transmitted with the event
message. As a consequence the message will not be recognized by the control system.
The Alarm detection enable screen is used to configure the detection of diagnostic
events but not the transmission of event messages to the bus. The latter is configured
on the Alarm broadcast enable screen, which is operated exactly in the same way as
the Alarm detection enable screen. Status information is only transmitted to the bus
if the Resource Block is in the Auto mode.