Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 179
For "Operating mode" = "Level" and "Medium type" = "Solid"
Process property Step response time / s
Very fast > 100 m (333 ft) /h 37
Fast > 10 m (33 ft) /h 37
Standard < 10 m (33 ft) /h 74
Medium < 1 m (3ft) /h 146
Slow < 0.1 m (0.3ft) /h 290
No filter / test < 1
For "Operating mode" = "Interface" or "Interface with capacitance"
Process property Step response time / s
Very fast > 10 m (400 in)/min 5
Fast > 1 m (40 in)/min 5
Standard < 1 m (40in) /min 23
Medium < 10 cm (4in) /min 47
Slow < 1 cm (0.4in) /min 81
No filter / test 2.2
Advanced process conditions
Navigation  Setup → Advanced setup → Level → Adv. conditions
Prerequisite Operating mode (→  159) = Level
Description Specify additional process conditions (if required).
Selection None
Oil/Water condensate
Probe near tank bottom
Build up
Foam (>5cm/0,16ft)
Factory setting None
Additional information Meaning of the options
Oil/Water condensate (only Medium type = Liquid)
Makes sure that in the case of two-phase media only the total level is detected (example:
oil/condensate application).
Probe near tank bottom (only for Medium type = Liquid)
Improves the empty detection, especially if the probe is mounted close to the tank
bottom.
Build up
Enables a safe empty-detection even if the end-of-probe signal has shifted due to build-
up.
Foam (>5cm/0,16ft) (only for Medium type = Liquid)
Optimizes the signal evaluation in applications with foam formation.