Operating menu Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
194 Endress+Hauser
Interface linearized
Navigation Setup → Advanced setup → Linearization → Interf. lineariz
Prerequisite Operating mode (→  159) = Interface or Interface with capacitance
Description Displays the linearized interface height.
Additional information The unit is defined in the Unit after linearization parameter →  192.
Maximum value
Navigation  Setup → Advanced setup → Linearization → Maximum value
Prerequisite Linearization type (→  191) has one of the following values:
Linear
Pyramid bottom
Conical bottom
Angled bottom
Horizontal cylinder
Sphere
Description Specify the maximum content of the vessel (100%) measured in the units after
linearization.
User entry –50 000.0 to 50 000.0 %
Factory setting 100.0 %
Diameter
Navigation  Setup → Advanced setup → Linearization → Diameter
Prerequisite Linearization type (→  191) has one of the following values:
Horizontal cylinder
Sphere
Description Specify tank diameter.
User entry 0 to 9 999.999 m
Factory setting 2 m
Additional information The unit is defined in the Distance unit parameter (→  159).