Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 197
Level (Manual)
Navigation Setup → Advanced setup → Linearization → Level
Prerequisite • Linearization type (→ 191) = Table
• Table mode (→ 195) = Manual
Description Enter level value of the table point (value before linearization).
User entry Signed floating-point number
Factory setting 0 %
Level (Semiautomatic)
Navigation Setup → Advanced setup → Linearization → Level
Prerequisite • Linearization type (→ 191) = Table
• Table mode (→ 195) = Semiautomatic
Description Displays measured level (value before linearization). This value is transmitted to the table.
Customer value
Navigation Setup → Advanced setup → Linearization → Customer value
Prerequisite Linearization type (→ 191) = Table
Description Enter linearized value for the table point.
User entry Signed floating-point number
Factory setting 0 %
Activate table
Navigation Setup → Advanced setup → Linearization → Activate table
Prerequisite Linearization type (→ 191) = Table
Description Activate (enable) or deactivate (disable) the linearization table.
Selection • Disable
• Enable