Micropilot FMR60B PROFINET with Ethernet-APL
20 Endress+Hauser
Gas phase Temperature Pressure
1 bar (14.5 psi) 10 bar (145 psi) 25 bar (362 psi)
+400 °C (+752 °F) –0.02 % +0.03 % +0.11 %
Water (saturated steam) +100 °C (+212 °F) +0.02 % - -
+180 °C (+356 °F) - +2.10 % -
+263 °C (+505 °F) - - +4.15 %
+310 °C (+590 °F) - - -
+364 °C (+687 °F) - - -
With a known, constant pressure, it is possible to compensate for this measured error with a
linearization, for example.
Mounting
Mounting location
A0016882
A Recommended distance from wall to nozzle outer edge ~ 1/6 of the vessel diameter. The device should never
be mounted closer than 15 cm (5.91 in) to the tank wall.
1 Use of a weather protection cover; protection from direct sunlight or rain
2 Installation in the center, interference can cause signal loss
3 Do not install above the filling curtain