Micropilot FMR60B PROFINET with Ethernet-APL
Endress+Hauser 39
Process connection UNI flange 316L
Seal T
p
Process pressure range
A0047726
FKM Viton GLT –40 to +130 °C (–40 to +266 °F) –1 to 3 bar (–14.5 to 43.5 psi)
FKM Viton GLT –40 to +150 °C (–40 to +302 °F) –1 to 3 bar (–14.5 to 43.5 psi)
FKM Viton GLT –40 to +200 °C (–40 to +392 °F) –1 to 3 bar (–14.5 to 43.5 psi)
EPDM –40 to +130 °C (–40 to +266 °F) –1 to 3 bar (–14.5 to 43.5 psi)
HNBR –20 to +150 °C (–4 to +302 °F) –1 to 3 bar (–14.5 to 43.5 psi)
FFKM Kalrez –20 to +150 °C (–4 to +302 °F) –1 to 3 bar (–14.5 to 43.5 psi)
FFKM Kalrez –20 to +200 °C (–4 to +392 °F) –1 to 3 bar (–14.5 to 43.5 psi)
The pressure range may be further restricted in the event of a CRN approval.
Integrated antenna, PEEK, 20 mm (0.75 in)
Process connection thread 3/4"
Seal T
p
Process pressure range
A0047832
FKM Viton GLT –40 to +150 °C (–40 to +302 °F) –1 to 20 bar (–14.5 to 290 psi)
FKM Viton GLT –40 to +200 °C (–40 to +392 °F) –1 to 20 bar (–14.5 to 290 psi)
FFKM Kalrez –20 to +150 °C (–4 to +302 °F) –1 to 20 bar (–14.5 to 290 psi)
FFKM Kalrez –20 to +200 °C (–4 to +392 °F) –1 to 20 bar (–14.5 to 290 psi)
The pressure range may be further restricted in the event of a CRN approval.
Integrated antenna, PEEK, 40 mm (1.5 in)
Process connection thread 1-½"
Seal T
p
Process pressure range
A0047833
FKM Viton GLT –40 to +150 °C (–40 to +302 °F) –1 to 20 bar (–14.5 to 290 psi)
FKM Viton GLT –40 to +200 °C (–40 to +392 °F) –1 to 20 bar (–14.5 to 290 psi)
FFKM Kalrez –20 to +150 °C (–4 to +302 °F) –1 to 20 bar (–14.5 to 290 psi)
FFKM Kalrez –20 to +200 °C (–4 to +392 °F) –1 to 20 bar (–14.5 to 290 psi)
The pressure range may be further restricted in the event of a CRN approval.
Dielectric constant
For liquids
ε
r
≥  1.2
Contact Endress+Hauser for applications with lower dielectric constants than indicated.
Mechanical construction
Dimensions
The dimensions of the individual components must be added together for the total dimensions.