4 Wiring PROline Promass 80
28 Endress+Hauser
4.2.3 HART connection
Users have the following connection options at their disposal:
• Direct connection to transmitter by means of terminals 26 / 27.
• Connection by means of the 4...20 mA circuit.
!
Note:
• The measuring loop's minimum load must be at least 250 Ω.
• The CURRENT SPAN function must be set to “4–20 mA” (individual options see device
function).
• See also the documentation issued by the HART Communication Foundation, and in
particular HCF LIT 20: “HART, a technical summary”.
Connection of the HART handheld communicator
See also the documentation issued by the HART Communication Foundation, and in
particular HCF LIT 20: “HART, a technical summary”.
Fig. 17: Electrical connection of the HART handheld communicator:
1 = HART communicator, 2 = power supply, 3 = shield, 4 = other evaluation devices or PLC with passive input
Connection of a PC with an operating software
In order to connect a personal computer with an operating software (e.g. “FieldTool”), a
HART modem (e.g. “Commubox FXA 191”) is needed.
Fig. 18: Electrical connection of a PC with an operating software:
1 = PC with an operating software, 2 = power supply, 3 = shield, 4 = other evaluation devices or PLC with
passive input, 5 = HART modem, e.g. Commubox FXA 191