Proline Promass I 300 PROFINET Commissioning
Endress+Hauser 107
Configuring the frequency output
Navigation
"Setup" menu → Pulse/frequency/switch output
Pulse/frequency/switch output
1 to n
Operating mode
→  107
Terminal number
→  107
Signal mode
→  107
Assign frequency output
→  108
Minimum frequency value
→  109
Maximum frequency value
→  109
Measuring value at minimum
frequency
→  109
Measuring value at maximum
frequency
→  109
Failure mode
→  109
Failure frequency
→  109
Invert output signal
→  109
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Operating mode Define the output as a pulse,
frequency or switch output.
Pulse
Frequency
Switch
Terminal number Shows the terminal numbers
used by the PFS output
module.
Not used
24-25 (I/O 2)
22-23 (I/O 3)
Signal mode Select the signal mode for the
PFS output.
Passive
Active
Passive NAMUR