Diagnostics and troubleshooting Proline Promass I 300 PROFINET
214 Endress+Hauser
Diagnostic information Remedy instructions
No. Short text
942 API density out of specification 1. Check process density with selected API commodity group
2. Check API related parameters
Measured variable status [from the factory]
1)
Quality Bad
Quality substatus Maintenance alarm
Coding (hex) 0x24 to 0x27
Status signal S
Diagnostic behavior Warning
Influenced measured variables
Mass flow
1) Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information Remedy instructions
No. Short text
943 API pressure out of specification 1. Check process pressure with selected API commodity group
2. Check API related parameters
Measured variable status [from the factory]
1)
Quality Bad
Quality substatus Maintenance alarm
Coding (hex) 0x24 to 0x27
Status signal S
Diagnostic behavior Warning
Influenced measured variables
• Oil density
• Water density
• GSV flow
• GSV flow alternative
• Mass flow
• Oil mass flow
• Water mass flow
• NSV flow
• NSV flow alternative
• External pressure
• S&W volume flow
• Reference density alternative
• Corrected volume flow
• Oil corrected volume flow
• Water corrected volume flow
• Oil volume flow
• Water volume flow
• Water cut
1) Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.