Description of device functions Proline Prosonic Flow 91
84 Endress+Hauser
11.10 Group COMMUNICATION
Functional description COMMUNICATION
!
Note!
The communication group is only visible if the HART option was selected in the CURRENT RANGE function.
TAG NAME Use this function to enter a tag name for the measuring device. You can edit and read this
tag name via the local display or the HART protocol.
User input:
Max. 8-character text, permitted characters are: A-Z, 0-9, +,-, underscore, space, period
Factory setting:
"_ _ _ _ _ _ _ _" (without text)
TAG DESCRIPTION Use this function to enter a tag description for the measuring device. You can edit and read
this tag description at the local display or via the HART protocol.
User input:
Max. 16-character text, permitted characters are: A-Z, 0-9, +,-, underscore, space, period
Factory setting:
"_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _" (without text)
FIELDBUS ADDRESS Use this function to define the address for the exchange of data with the HART protocol.
User input:
0 to 15
Factory setting:
0
!
Note!
Addresses 1 to 15: a constant 4 mA current is applied.
WRITE PROTECT Use this function to activate HART write protection.
Options:
OFF = function can be edited/read via the HART protocol
ON = HART protocol write-protected (only readable)
Factory setting:
OFF
MANUFACTURER ID Use this function to view the manufacturer number in decimal numerical format.
Display:
– Endress+Hauser
– 17 ( 11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display:
62 hex ( 98 dez) for Prosonic Flow 91