11 Operation via FOUNDATION Fieldbus Proline Prowirl 72 FOUNDATION Fieldbus
100 Endress + Hauser
Sensor Data -
Nominal
Diameter
AUTO - OOS The nominal diameter of the sensor appears on the display.
Display:
e.g. "DN 25 mm - 1 Inch"
" Caution!
Do not change this value, because a change will inevitably affect the
accuracy of the measuring device.
Sensor Data -
Meter Body MB
AUTO - OOS The type of meter body (MB) of the sensor appears on the display.
Display:
e.g. 71
! Note!
Use this function to specify the nominal diameter and the sensor type.
The type of meter body (MB) is also indicated on the nameplate
" Caution!
Do not change this value, because a change will inevitably affect the
accuracy of the measuring device.
Sensor Data -
Temperature
Coeff.
AUTO - OOS The temperature effect on the calibration factor appears on the display.
Due to changes in temperature, the meter body expands differently,
depending on the material. The expansion has an effect on the K-factor.
Display:
4.88 e
-5
/K 4.88 10
-5
(stainless steel)
2.6 e
-5
/K 2.6 10
-5
(Alloy C-22)
" Caution!
Do not change this value, because a change will inevitably affect the
accuracy of the measuring device.
Transducer Block "Flow" (Endress+Hauser parameters) / base index 500