6 Commissioning Proline Prowirl 72 FOUNDATION Fieldbus
38 Endress + Hauser
5. Using the DEVICE_ID noted, identify the field device and assign the desired tag name
(PD_TAG) to the fieldbus device in question.
Factory setting: E+H_PROWIRL_72_xxxxxxxxxxx
A0003789
Fig. 25: Screen display in the configuration program "NI-FBUS Configurator" (National Instruments) after the
connection has been established
Configuring the "Resource Block" (base index 400)
6. Open the Resource Block.
7. When the device is delivered, the hardware write protection is disabled so the write
parameters can be accessed via the FOUNDATION Fieldbus. Check the status via the
WRITE_LOCK parameter:
Write protection enabled = LOCKED
Write protection disabled = NOT LOCKED
Disable the write protection if necessaryPage 35.
8. Enter the desired name for the block (optional).
Factory setting: RESOURCE_ xxxxxxxxxxx
9. Set the operating mode in the MODE_BLK parameter group (TARGET parameter) to AUTO.
Configuring the "Transducer Blocks"
The individual Transducer Blocks comprise various parameter groups arranged by device-specific
functions:
The following section describes an example for the Transducer Block "Flow" (base index 500).
Flow measurement Transducer Block "Flow" (base index: 500)
Totalizer Transducer Block "Totalizer" (base index: 600)
Local display functions Transducer Block "Display" (base index: 700)
Diagnostic functions Transducer Block "Diagnosis" (base index: 800)
Service functions Transducer Block "Service" (base index: 900)