Trouble-shooting Proline t-mass 65 PROFIBUS DP/PA
96 Endress+Hauser
691 S: SIM. FAILSAFE
!: # 691
0x48
0x49
0x4A
UNCERTAIN Substitute set O.K.
Low
High
Simulation failsafe
active
Cause:
Simulation of failsafe mode (outputs) is active.
Remedy:
Switch off simulation.
Access:
SIMULAT. SYSTEM FAILSAFE MODE
( OFF)
692 S: SIM. MEASURAND
!: # 692
0x60
0x61
0x62
UNCERTAIN Simulated
Value
O.K.
Low
High
Simulation
measured value
active
Cause:
Simulation of the measured value is active.
Remedy:
Switch off simulation.
Access:
SIMULAT. SYSTEM SIM. MEASURAND
( OFF)
698 S: DEV. TEST ACT.
!: # 698
0x60
0x61
0x62
UNCERTAIN Simulated
Value
O.K.
Low
High
Device test via
Fieldcheck active
Cause:
The measuring device is being checked on site via
the test and simulation device.
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Remedy / spare parts
Spare parts ä 99
Quality code (HEX)
Measured variable status
Quality status
Quality substatus
Limits