Function group
BATCHING
BATCH
VARIABLE
In this function, the batching mode can be activated or switched off.
Note!
If the batching mode is activated, the “BATCHING” Function group is first
shown on the display when entering the operating matrix. The “BATCH
VARIABLE” function then moves into first position within this group.
6
OFF
VOLUME
BATCH
QUANTITY
This function is used to set the required batching quantity.
Note!
Relay 2 can be assigned as a “BATCH CONTACT” (see page 62).
6
5-digit number with floating decimal point (e.g. 240.00 l)
Unit selection see function “VOLUME UNIT
Factory setting:
0.0000
[unit]
7
Dispay showing which function is assigned to Relay 2.
BATCH
PREWARN
In this function a
pre-batch
quantity can be defined which is used for two-stage
batching cycles (see page 63).
Note!
Relay 1 can be assigned as a “PREBATCH CONTACT” (see page 58).
6
5-digit number with floating decimal point (e.g. 200.00 l)
Unit selection see function “VOLUME UNIT
Factory setting:
0.0000
[unit]
7
Dispay showing which function is assigned to Relay 1.
Note!
Note!
Note!
6 Description of Functions Promag 33
64 Endress+Hauser