Chapter 4 Function Introduction SuZhou Eshine Elevator Components Co., Ltd.
36 YS-K01 Door Controller User Manual
4.4 Group P3 OD Curve Parameters
Refer to section 5.3.1 for the OD curve optimal.
Code Name Description Range
factory setting
P3.00
OD start distance
09999240
P3.01 OD start speed 0.00
15.00 Hz
2.50Hz
When the door is in the OD start distance, the door machine will run at the OD start speed.
P3.02 OD acceleration (Acc) time 0.1
99.9s
0.8s
OD Acc time is the time accelerated from zero frequency to the maximum frequency.
P3.03 OD speed 0.00
P0.07
20.00Hz
It defines the high operating speed (frequency) during OD process.
P3.04 OD deceleration (Dec) point position 50.0
90.0 door width
72.0%
When the pulse number P3.04×door width, the door machine will decelerate from P3.03 (OD
speed) to P3.06 (Creeping speed at OD ending). The bigger P3.04 is set, the shorter Dec distance is.
P3.05 OD Dec time 0.1
99.9
1.0s
OD Dec time is the time decelerated from maximum frequency (P0.07) to zero frequency.
P3.06 Creeping speed at OD ending 0.00
15.00
2.00Hz
It defines the low creeping speed (frequency) of door machine during OD process.
P3.07 OD limit point 80.0
99.9 door width
90.0%
When door position pulse P3.07×door width, the door machine will output OD arrival signal.
P3.08 Re-open curve high-speed area 10.0
90.0 door width
70.0%
P3.08 defines the re-open curve high-speed area at re-opening.
This parameter setting may improve the re-open efficiency.
Example:
P3.08 = 70.0%, which represents when the door position is in 030% range (100%-70%), it will auto
accelerate to high speed at re-open; when the door position is in 30100% range, it will
auto-calculate out the run curve according to the present position at re-open.