Chapter 2 Installation and Wiring SuZhou Eshine Elevator Components Co., Ltd.
2 YS-K01 Door Controller User Manual
Chapter 2 Installation and Wiring
Do not install if the controller is imcomplete or impaired.
Make sure that the controller is far from the explosive and combustible things.
Bare metallic part of the power terminal wiring should be with insulating tape to wrap up.
Only qualified electrical engineer can perform wiring job.
Only when the power supply is completely cut-off 10 minutes later can you do the wiring job.
The communication wire must use shielded twisted-pair cable with 2030mm twisted interval, and
the shielding layer must be grounded.
The encoder must use a shielded wire, and the shielding layer must be connected to ground
reliably.
Do not connect the power input terminals to the output terminals (U/V/W) of the controller.
The earth terminal PE of the controller must be reliable earthing. It must use two separate earth
wire due to the leakage current from the controller to ground.
Do not touch the wire terminals of the controller when it is live. The main circuit terminals is neither
allowed connecting to the enclosure nor short-circuiting.
Only when the controller terminal cover has been fitted can you switch on AC power source. Do not
remove the cover after power is switched on.
Do not play metal into the controller when installing.
Do not start and shutdown the controller by connecting and disconnecting the contactor.
Detection of signals during the operation shall only be conducted by qualified technician.
Do not do dielectric strength test on the controller.
Ensure the installation site meeting the following requirements:
Do not install at the direct sunlight, moisture, water droplet location;
Do not install at the combustible, explosive, corrosive gas and liquid location;
Do not install at the oily dust, fiber and metal powder location;
Be vertical installation on fire-retardant material with a strong support;
Make sure adequate cooling space for the controller so as to keep the ambient temperature
among - 10+ 40;
Install at where the vibration is lesser than 5.9m/s
2
(0.6g).
Danger
Warning