Chapter 5 Controller Debugging SuZhou Eshine Elevator Components Co., Ltd.
―50― YS-K01 Door Controller User Manual
Step 4:
To test the operation, press key or key, manually open/close the door to
observe the OD/CD curve, and then properly change the OD/CD Acc/Dec point and time. Refer
to Group P3 and Group P4 for more details.
Step 5:
According to the actual need of elevator main control cabinet, ensure the door machine
arrival signal (relay output selection: P6.00=0 normally open, P6.00=1 normally closed, it defaults
normally closed.)
Step 6:
Enter elevator operation, set P0.06=1 to terminal control mode.