A951 54 532081 - RevA
Translation of the original instructions
ENGLISH
11. FINAL OPERATIONS
1. Press the front cover on.
2. Press the top and bottom slot covers on.
3. For doors in “low energy mode, make sure that the
forces generated by the leaf are within the limits
permitted by the regulations. Use an impact
force tester in accordance with EN 12453: 2002
and EN 12445: 2002. For non-EU countries, of
there are no specific local regulations, the force
must be less than 67 N.
4. For doors that are not in “low energy mode, make
sure that the test object is detected in all areas
covered by the door movement.
5. Highlight all areas with adequate warning signs in
which there are still residual risks, even if all pos-
sible safety measures having been adopted. In
particular, for doors less than 2 meters high, apply
the hazard warning pictograms in correspondence
with the arm movement area.
6. Place a “DANGER, AUTOMATICALLY CONTROLLED”
sign in a prominent position on the door.
7. Attach the CE marking on the door.
8. Fill out the EC declaration of conformity and the
system register.
9. Give the EC Declaration, the system register with
the maintenance plan and the instructions for use
of the automation to the system owner/operator.